SCHMERSAL 2356 (24-230VAC/DC)
SCHMERSAL 2356 SAFETY RELAY
- Monitoring of BNS range magnetic safety sensors
- 3 safety contacts, STOP 0
- 2 Signalling outputs
ORDERING DATA | |
---|---|
Note (Delivery capacity) | Not available! |
Product type description | AES 2356 UE: 24…230V AC/DC |
Article number (order number) | 101181683 |
EAN (European Article Number) | 4030661323145 |
eCl@ss number, version 12.0 | 27-37-18-19 |
eCl@ss number, version 11.0 | 27-37-18-19 |
eCl@ss number, version 9.0 | 27-37-18-19 |
ETIM number, version 7.0 | EC001449 |
ETIM number, version 6.0 | EC001449 |
Available until | 01.12.2021 |
APPROVALS – STANDARDS | |
---|---|
Certificates | BG cULus EAC |
GENERAL DATA | |
---|---|
Standards | BG-GS-ET-14 BG-GS-ET-20 EN IEC 62061 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress | BG-GS-ET-14 IEC 60947-5-3 |
Enclosure material | Glass-fibre, reinforced thermoplastic |
Material of the contacts, electrical | Ag-Ni 10 and 0.2 µm gold-plated |
Gross weight | 342 g |
GENERAL DATA – FEATURES | |
---|---|
Stop-Category | 0 |
Wire breakage detection | Yes |
Cross-circuit detection | Yes |
Feedback circuit | Yes |
Automatic reset function | Yes |
Start-up test | Yes |
Reset after disconnection of supply voltage | Yes |
Integral system diagnostics, status | Yes |
Number of LEDs | 1 |
Number of normally closed (NC) | 2 |
Number of normally open (NO) | 2 |
Number of undelayed semi-conductor outputs with signaling function | 2 |
Number of safety contacts | 3 |
Number of signalling outputs | 2 |
Safety classification | |
Standards | EN ISO 13849-1 EN IEC 61508 |
Safety classification – Relay outputs | |
Performance Level, up to | d |
Category | 3 |
PFH value | 1.00 x 10⁻⁷ /h |
Notice | for max. 50,000 switching cycles/year and max. 80% contact load |
Safety Integrity Level (SIL), suitable for applications in | 2 |
Mission time | 20 Year(s) |
MECHANICAL DATA | |
---|---|
Mechanical life, minimum | 20,000,000 Operations |
Mounting | Snaps onto standard DIN rail to EN 60715 |
MECHANICAL DATA – CONNECTION TECHNIQUE | |
---|---|
Termination | rigid or flexibleScrew terminals M20 x 1.5 |
Terminal designations | IEC/EN 60947-1 |
Cable section, minimum | 0.25 mm² |
Cable section, maximum | 2.5 mm² |
Tightening torque of Clips | 0.6 Nm |
MECHANICAL DATA – DIMENSIONS | |
---|---|
Width | 45 mm |
Height | 100 mm |
Depth | 121 mm |
AMBIENT CONDITIONS | |
---|---|
Degree of protection of the enclosure | IP40 |
Degree of protection of the mounting space | IP54 |
Degree of protection of clips or terminals | IP20 |
Ambient temperature, minimum | +0 °C |
Ambient temperature, maximum | +55 °C |
Storage and transport temperature, minimum | -25 °C |
Storage and transport temperature, maximum | +70 °C |
Resistance to vibrations | 10…55 Hz, Amplitude 0.35 mm, ± 15 % |
Restistance to shock | 30 g / 11 ms |
AMBIENT CONDITIONS – INSULATION VALUES | |
---|---|
Rated impulse withstand voltage Uimp | 4 kV |
Overvoltage category | III |
Degree of pollution | 2 |
Add comment